Multi-line 2 CGC 400 Application Software series 1.x.

このソフトウェアは以下のDEIF製品に適用されます。

ダウンロードされようとしています 1.14.1

最終版以降に行われた主な変更は以下の通りです。

Changes:

  • Improved precision of display readout of total energy counter.
  • Added new view line for absolute running hour counter with minutes.

Corrections:

  • Multi-input HW limit erroneous warning at power on.
  • EIC measurement alarms are now inhibited during EIC communication failure.

 

バージョン 日付 説明

1.14.1

04/01/2018

Changes:

  • Improved precision of display readout of total energy counter.
  • Added new view line for absolute running hour counter with minutes.

Corrections:

  • Multi-input HW limit erroneous warning at power on.
  • EIC measurement alarms are now inhibited during EIC communication failure.

 

1.14.0

15/08/2017

Version 1.14.0 based on version 1.13.1

New features:

  • Phase sequence error is now detected and handled at both sides of the breakers (common alarm extended to two separate alarms in menu 2150).

Changes:

  • Phase sequence error is no longer detected when the voltage or frequency is outside volt./ frequency ok values.

Corrections:

  • Support of checksum in TSC1 telegram added for Volvo Penta EMS 2. Merge from SIPC 0497.
  • Phase sequence error status texts could appear even if they should be inhibited. GB would not close because of phase sequence error even if it was inhibited.

 

1.13.1

19/05/2016

Corrections:

  • Initiated cool-down cannot be aborted when a wire break fail class alarm is present.
  • Running hours offset is now stored and handled correct.
  • Scania EMS2 KWP2000 log clearing now possible.
  • Inhibit evaluation added to a number of AC alarms.
  • Genset data (e.g. oil pressure) was not displayed/updated correctly in the USW.
  • Negative values in range -1.0 to 0.0 showed correctly in the display.
  • Corrected "Limits relay" handling when setting up alarm output.
  • A problem with downloading new language from the USW has been corrected. The Language download returned “burn error”.

1.13.0

24/02/2015

Changes:

  • Scaling range 1 kV - 75 kV changed to 0.4 kV - 75 kV.

Corrections:

  • Attempting to stop during idle at start would ramp the engine to full speed and keep running, if the running detection speed had been reached during idle run
    Running hours counter not saved, and total energy counter not shown correctly in display
  • Space padding in master texts has been removed. Further when writing translations, space padding is removed from each text programmed 

1.12.0

27/11/2014

New features:

  • MTU ADEC CANopen engine communication interface now supports shutdown override.

Changes:

  • Mains voltage failure limit changed from 80-100 % to 40-100 %

Corrections:

  • Inverse Time Overcurrent protection aligned with IEC 60255 part 151 (AGC 200)
  • MTU MDEC 302/303 protocols battery voltage measurement corrected.
  • Regarding Idle start timer: Timer now resets if the Start Off timer is running.
  • AMF sequence was incorrect in some cases.
  • Start enable has to be energised to activate the regulation.
  • Option H5/H7, MTU alarm "AL Speed Demand Failure" no longer present all the time.
  • The reactive power was wrong when the phase rotation was L1L3L2.
  • Unit could reboot if a Modbus command was sent while 'Inhibit modbus commands' was active

1.10.0

08/04/2014

Changes:

  • Language translation changed. From now on it is not possible to select a different font.
  • The two fonts are now merged, containing all previously used characters.
  • The new font contains some new characters. If any unsupported signs are written to the device the signs will appear as ' ' (space). USW 3.37.0 or higher required.

Corrections:

  • Several menu texts were not using translations - Corrected.
  • Parameter outputs A and B could not be configured as "Limits" - Corrected.
  • Option C2 inverse over-current malfunctions when using "Customer" defined curve - Corrected.
  • The Fuel Pump Logic feature now disabled under power up while measurements are invalid.
  • Relay setting error could occur each time the unit starts up - Corrected

1.01.0

26/11/2013

New features:

  • RPM based on calculation from the AC reading

Corrections:

  • Pre-configuration of RMI 6-8 corrected

このページではお使いの製品のソフトウェアアップデートをダウンロードでき、また設定、不具合の検出、製品の構成を支援する様々なユーティリティーツールおよびアドオンを入手できます。

ユーザーは当社製品のすべてをアップデートできないことにご注意ください。また、当社製品のすべてにユーティリティーツールが備わっているわけではありません。このため、このページのリストを当社の製品プログラムの概要とみなすことはできません。

DEIFはお客様のダウンロードとご使用になられたEメールアドレスを今後のアップデートのお知らせをお送りする目的で、リクエストがあれば登録いたします。

DEIFは製品アップロードまたはユーティリティーツールの使用の失敗によるいかなる結果に対しても責任を負いません。また、DEIF A/Sはソフトウェアアップデートにより製品の動作に起こる変更の結果に対する責任を負いません。試運転前に正しい設定と構成を確実に行うのは、常にユーザーの責任です。ソフトウェアのバージョンログを確認してから製品のアップデートを行うようにしてください。

www.deif.comからダウンロードしたソフトウェアのライセンス契約

ダウンロードしたソフトウェアはDEIFの財産であり続けます。本ソフトウェアを商用目的で配布したり、全部または一部を変更または再利用したり、第三者に売却してはなりません。

いつもながら、当社が提供する改良点をインストールしていただき、お使いのDEIF製品を最大限に活用していただくことを推奨いたします。

すべての改良ソフトウェアはご都合の良い時に、無料で www.deif.com にて、「ソフトウェア」、次に「ソフトウェアダウンロード」に進むことでダウンロードできます。

お使いの製品の関連ソフトウェアを見つける際に質問または問題がある場合は、お気軽にDEIF A/S (+45 96149614)までお電話されるか、または関連の最寄りのDEIF営業所までお電話ください。あるいは、support@deif.com.までEメールをお送りいただければ、常にお客様をサポートさせていただきます。

プレスリリース、2015年6月

特に「旧式」DEIF A/S ML‐2製品に関連する製品改良.